HGL36100CU44X Square D PowerPact H 100A 3-Pole 600V Breaker — MicroLogic 6.2A LSIG, 100% Rated

Need a 100A, 3-pole PowerPact H breaker with electronic trip? The HGL36100CU44X is the one. It mounts as a unit breaker with mechanical lugs on both line and load, so it drops straight into your switchboard or panelboard, and it's rated for reverse-fed setups when you need them. The MicroLogic 6.2A trip unit gives you full LSIG — long-time, short-time, instantaneous, and ground fault — plus an ammeter right on the breaker so you can read load current without pulling a meter.

Because it's a 100%-rated breaker, you can run it at full nameplate continuously — no 80% derate to work around when you're sizing the feeder. Interrupting capacity is G-tier: 65kA at 240V, 35kA at 480V, 18kA at 600V.

Common Applications

  • Feeder and branch protection in commercial and industrial panels
  • Direct replacement for existing H-Frame MicroLogic breakers
  • Circuits that need ground-fault protection built into the breaker
  • Full continuous-load feeders where an 80% breaker won't cut it
  • Motor and HACR equipment feeds

Key Features

  • MicroLogic 6.2A trip: Field-adjustable LSIG protection with an on-board ammeter.
  • 100% rated: Run it at full nameplate continuously, no derate.
  • Drops right in: Unit mount with line and load lugs; reverse-feed capable.
  • Tough interrupting: 65kA@240V, 35kA@480V, 18kA@600V.
  • Push-to-trip + Visi-Trip: Manual trip check and clear fault indication.

Specifications

  • Manufacturer: Square D by Schneider Electric
  • Part Number: HGL36100CU44X
  • Frame: PowerPact H-Frame
  • Amperage: 100A
  • Poles: 3-pole, 3-phase
  • Voltage: 600VAC (250VDC rated)
  • Trip Unit: MicroLogic 6.2A electronic, LSIG + ammeter
  • Continuous Rating: 100%
  • AIC: 65kA@240V / 35kA@480V / 18kA@600V / 20kA@250VDC
  • Lugs: Line and load, AWG 14–3/0 Al/Cu
  • Mounting: Unit mount
  • Listings: UL 489, CSA, NEMA, NOM, IEC 60947-2, CE
  • HACR Rated: Yes

Product Identification

  • Country of Origin: Mexico
  • Dimensions: 6.4 in H × 4.12 in W × 4.36 in D
  • Net Weight: 4.8 lb

FAQ

Will this drop into my H-Frame panel? Yes — it's a unit-mount H-Frame breaker with standard line and load lugs.

Can I reverse-feed it? Yes, the HGL36100CU44X is suitable for reverse-fed applications.

Does it have ground-fault protection? Yes. The MicroLogic 6.2A is a full LSIG trip unit, so ground fault is built in.

What's the interrupting rating? 65kA at 240V, 35kA at 480V, and 18kA at 600V.

Electronic or thermal-magnetic? Electronic. The CU44X build is MicroLogic 6.2A and 100% rated, not the thermal-magnetic HGL36100.

What wire does it land? AWG 14–3/0 aluminum or copper on the standard lugs.